Current Carrying Capacity
Homepage → Current Carrying Capacity
Technical Specification
About Cable
Nom. Cross-Section (mm²) | Group 1 | Group 2 | Group 3 | |||
---|---|---|---|---|---|---|
One more single core cables and insulated wires laid in duct | Multi core cables, e.g. PVC-sheated cables, flexible cables, building cables, mobile cables | Single-core cables freely installed in air, hereby the cables are installed with in termediate spaces of the cable diameter as a minimum, as well as singlecore wiring in switching and distribution systems | ||||
Current Carrying Cap. (A) | Protective Fuse (A) | Current Carrying Cap. (A) | Protective Fuse (A) | Current Carrying Cap. (A) | Protective Fuse (A) | |
0,05 | 1 | - | 1 | - | 2 | - |
0,14 | 2 | - | 2 | - | 3,5 | - |
0,25 | 4 | - | 4,5 | - | 6 | - |
0,34 | 6 | - | 6 | - | 9 | - |
0,5 | 9 | - | 9 | - | 12 | - |
0,75 | 12 | - | 12 | 10 | 15 | 10 |
1 | 15 | 10 | 15 | 10 | 19 | 16 |
1,5 | 18 | 16 | 18 | 16 | 24 | 20 |
2,5 | 26 | 25 | 26 | 25 | 32 | 25 |
4 | 34 | 25 | 34 | 25 | 42 | 35 |
6 | 44 | 35 | 44 | 35 | 54 | 50 |
10 | 61 | 50 | 61 | 50 | 73 | 63 |
16 | 82 | 80 | 82 | 63 | 98 | 80 |
25 | 108 | 100 | 108 | 80 | 129 | 100 |
35 | 135 | 125 | 135 | 100 | 158 | 125 |
50 | 168 | 160 | 168 | 125 | 198 | 160 |
70 | 207 | 200 | 207 | 160 | 245 | 200 |
95 | 250 | 250 | 250 | 200 | 292 | 250 |
120 | 292 | 250 | 292 | 250 | 344 | 315 |
150 | 335 | 315 | 335 | 315 | 391 | 355 |
185 | 382 | 355 | 382 | 355 | 448 | 400 |
240 | - | - | 453 | 425 | 528 | 500 |
300 | - | - | 523 | 500 | 308 | 600 |
400 | - | - | - | - | 726 | 630 |